Description
The Notifier NFW-50X is a next-generation addressable fire alarm control panel (FACP) designed for small commercial and institutional applications. It supports up to 50 addressable devices and includes a pre-installed IPOTS-COM dual communicator for internet and phone line connectivity, offering enhanced programming, monitoring, and cost-saving communication options.
Technical Specifications
| Condition |
New/Never Used Surplus |
| Brand |
Notifier |
| Category |
|
| Part Number |
NFW-50X |
| Subcategory |
Fire Alarm Control |
| Series |
Notifier FireWarden |
| Device Capacity |
50 addressable devices (detectors/modules) |
| Protocols Supported |
FlashScan and CLIP
|
Power Input
|
120/240 VAC (auto-sensing), 50/60 Hz, 3.25 A |
| NAC Circuits |
2 Class A/B, 250 mA each (2.5 A shared capability) |
| System Output |
2.7 A (NACs + ANN-BUS shared) |
| Communication |
Built-in IPOTS-COM (IP + POTS), optional cellular |
| Relays |
2 programmable Form-C, 1 fixed trouble relay |
| Battery Support |
(2) 12 V, 7–18 AH lead-acid batteries |
| Programming Access |
USB port, Ethernet (via IPOTS-COM) |
| Tools |
FS-Tools Upload/Download Utility |
| Dimensions (W×H×D) |
23 × 20 × 7 in |
| Weight |
28 lbs |
Information About NFW-50X
The NFW-50X replaces the earlier NFW-50 model in the FireWarden Series and supports both FlashScan and CLIP protocols for flexibility with Notifier devices. It features two Class A/B NAC circuits, providing 250 mA per circuit (2.5 A shared for special applications) and 2.7 A total system output across NACs and ANN-BUS. The panel accepts 120/240 VAC auto-sensing input, and can house two 18 AH batteries internally for backup power. The included IPOTS-COM communicator supports POTS and IP alarm signaling, reducing reliance on costly dedicated phone lines while providing optional cellular communication. The panel offers two programmable Form-C relays and one fixed trouble relay, with USB and Ethernet connectivity for remote/local programming via FS-Tools software.
Key Features:
- Supports 50 Addressable Devices: Accepts any combination of detectors and modules on a single SLC loop.
- Dual Communication Protocols: FlashScan and CLIP support for broad Notifier device compatibility.
- Pre-Installed IPOTS-COM: Built-in dual communicator (IP + POTS) with optional cellular via CLSS Pathway.
- Flexible Power Input: Accepts 120/240 VAC auto-sensing at 50/60 Hz, 3.25 A max.
- Two Class A/B NAC Circuits: Each rated at 250 mA; total shared output 2.7 A for NACs and ANN-BUS.
- Battery Backup Support: Holds two 12 V, 18 AH batteries for 24 V backup (7–18 AH supported).
- Programming and Diagnostics: USB and Ethernet access for full programming and system diagnostics via FS-Tools.
- Integrated Relays: Two programmable Form-C relays for custom logic and one fixed trouble relay.
- Event History Storage: USB port enables history export, status review, and walk-test data access.
- UL and NFPA Compliant: Listed for use in commercial fire detection applications across the U.S. and internationally.
The NFW-50X delivers enhanced control, programming flexibility, and modern connectivity in a compact, intelligent FACP designed for advanced fire system performance.